Fire Detection & Alarm System

Intelligent Addressable Fire Alarm Control Panel

The FACP is designed to provide early warning fire detection, to quickly identify the location of fire and provide user
definable text informing the occupants of the building of potential smoke spread. Simultaneously.
The LF-X500 FACP comes with 1, 2, or 4 loop with 254 devices per loop comprise of a range of analogue addressable, microprocessor based fire alarm
control equipment to offer flexibility in both design and operation. The System is modular concept for easy tailoring of
system design, to meet the full requirements of the project. The FACP Intelligent Fire Alarm Control Panel is designed
and manufactured to meet the requirement of BS EN54 Part 2&4.

Datasheets

Matrix Network Vision Annunciator

The large, full color graphical display with touch screen functionality, delivers information on the status of the fire alarm system to single or multiple locations. Matrix Vision Annunciator can be configured to offer full display and control to replicate the functionality of the Fire Control panel or to operate as a simple, display-only device for applications where access to control the Fire Alarm system would be inappropriate.

  • Robust, full color, 7” 800 x 480 touch screen graphical display
  • Replicates information displayed at the panel
  • Automatic display brightness adjustment
  • Internal buzzer
  • Connects via control panel network terminals
  • Low current, 24V DC powered
  • Enable key-switch
  • Sheet steel enclosure.
  • Surface or semi-flush enclosure options available
Datasheets Manuals

White Eagle Control Panel Series

EAGLE Series is a conventional fire detection and indication panel that has Satarted 1 to 8 fixed Zone and is expanded to 16 zones. EAGLE is based on a modular principle – a power unit, a control panel, zone/sounder expanders, an indication module and battery space. A detailed LED indication shows the status of the system, divided in two groups – for technician level and for monitor and observer level. An appropriate mode for zone detector testing by a single person has been implemented – One Man Test. Control and indications can be doubled at a remote site up to 1000m away with the help of a repeater. The panel has been designed to operate with one 12 V battery back-up power, which reduces the costs by the value of one battery per system.  The EAGLE is suitable for vast range of applications –Small Shop to big office buildings, Banks, schools, supermarkets and other with over 3000m2.

  • 1-16 Fixed Zones
  • Supports up to 32- 512 detectors
  • Unlimited call points
  • 1 “fire” and 1 “fault” relay outputs
  • 4 monitored sounder outputs
  • Active EOL allowing continuous monitoring of inputs
  • Walk test
  • LED indication
  • Levels of access protected by means of security key
  • Plastic box
Details
Photoelectric Smoke Detector

The LIFECO LE-ALN-V Photoelectric Smoke Sensor is particularly suited to detecting optically dense smoke typical of fires involving materials such as soft furnishings, plastic, foam or other similar materials which tend to smoulder and produce large visible smoke particles. LIFECO’s unique design allows fast response to flaming fires as well as smouldering fires while eliminating false alarms.

 

Heat Detector

The LIFECO LE-ATJ-EA Sensor provides accurate temperature measurement data to the fire alarm control panel. This sensor is particularly suited to environments where smoke detectors are unsuitable because of the presence of system or cooking fumes such as in a kitchen.

Multi Criteria Sensor

The CO, COHb, Smoke, & Heat Multi- Criteria Sensor is particularly suited for detecting smoke produced by a wide range of combustibles found in various applications. Temperature monitoring is achieved by a thermistor placed for optimum sensitivity. The sensor is also suited for detecting deadly levels of CO.

Conventional Fire Alarm Bell

LIFECO Fire Alarm Bells are specially designed for fire alarm applications. The LIFECO bell gongs are made of alloy steel to give the loud tones necessary in fire alarm systems. It is available in three gong sizes for different applications. For weather-proof application LIFECO offers an optional weatherproof back box.

Sounder

With a low profile sleek design, the LIFECO Sounder is ideal for standard installations and where aesthetics are an important consideration.Suitable for conventional sounder circuits, notification alarm circuits and 2-Wire alarm systems. LIFECO Sounder’s low operating current means it can easily be interfaced onto Analogue Addressable fire alarm systems with a suitable output module. The LIFECO sounder can be flush mounted using a standard electrical single gang back box and surface mounted with the default back box.

Manual Call Point (MCP50)

The White Eagle MCP50 is a manual call point designed to work in conventional fire alarm systems. The call point has a re-settable fragile working element to ensure reliable and safe operation. The LED indication informs the user for fire and test events.

Addressable Sounder

The LF-X5320 Addressable Sounder is alarm warning device used to notify persons in the vicinity of the occurrence fire emergency in order the person to take appropriate measures. The unit adopt multi-application device starting from the types, parameters and wiring layout in single unit. Parameters can be configured according to the requirement which include alarm tone from 17 different tones, single address or dual address mode and also setting of power mode to low current consumption in a simple programing.

Addressable Sounder Strobe Model

The LF-X5301 Intelligent Sounder Strobe is alarm warning device used to notify persons in the vicinity of the occurrence fire emergency in order the person to take appropriate measures. The unit adopt multi-application device starting from the types, parameters and wiring layout in single unit. The LF-X5301 can change into different alarm warning types such as sounder-strobe type, sounder type or strobe type using programming tool. In addition, parameters can be configured according to the requirement which include alarm tone from 17 different tones, single
address or dual address mode and also setting of power mode to low current consumption in a simple programming.

Addressable Single I/O Module

The LF-X5210 Addressable Single Input/output Module is characterized as one input or output volt free relay and control module. The unit is normally used for overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMS and etc. The unit has built-in feedback signal feature, according to the pre-configured interface module command fire scenario, the alarm controller send out start command to the equipment required to start. After receiving the command, output module enables its relay to change state. Once the module is under control and operated a confirmation signal will be sending back to the alarm controller. In addition, the unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input
signal line.

12 In 2 Out Module

The LF-X5223 Addressable 12 Input/ 2output Module is characterized as 12 inputs power limited and 2 outputs volt free relay. It is used to acknowledge normally open monitor signal from interface equipment then sending communication signal to the control panel, ideally for monitoring sprinkler system, pressure switch, position switch, signal valves and other third-party equipment such as conventional panel. The output relay is normally used for overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMS and etc… In addition, the unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input signal line. All interfaces can be seen on the panel and can be configured on the command builder to create requirement for fire event scenario, as each circuit has its own unique address, this module occupied 14 address.

Backbox Model

The LF-X5990 is used for all LF-X52 series of addressable modules to provide surface mount installation. This box back has a two knock holes for cable entrance.

• Backbox compatible for LF-X52 Module Series
• Constructed using high quality plastic
• No electrical circuit
• Fit on one gang backbox
• Easy to install

Graphic Monitoring Software

LF-X500 panel design a new set of software engineering monitoring system, through good architecture designed to meet various requirements of stand-alone monitoring system, network and other aspects of the system, the system is easy to operate, the interface is beautiful and generous. The graphic display device is connected with the fire alarm panel through the RS232 interface, and is connected with the remote monitoring center through the RJ45 network port, so as to realize the real-time monitoring of the fire alarm panel and the field equipment information.

Intelligent Graphic Mimic Panel

LF-X5331 Intelligent Graphic Repeater Panel is designed with built-in MCU processor and it can fast relay response with simultaneous audible and visual signal output. This repeater panel can also program to limit the zone display from All Zones into a particular zone or device. Also it can supervise and indicate the groups as well as device. The unit is connected through the communication loop of LF-X500 Intelligent control panel along with the devices and can install up to 254 units per loop. The repeater panel can be used whenever there is a need to relay information to multipoint informing key personnel.

Handheld Programmer

The LF-X5932 is the general purpose programming tool use for LF-X family products. This unit is designed to suit for entering device parameters such as address, sensitivity, mode and types to meet the site situation and environmental requirements. In addition, the programmer is capable to read the previous encoded parameters to use for testing application and troubleshooting purposes.

Duct Probe

A HVAC system supplies conditioned air to virtually every part of a building. Any smoke introduced into this air duct system is thus spread to the entire building. The Duct Probe is designed such that samples of air passing through the duct are constantly monitored by the inside Optical Smoke Detector. When sufficient smoke is sensed, an alarm signal is initiated at the Fire Alarm Control Panel monitoring the detector, and appropriate action can be taken to shut off fans and blowers and change over air handling system, etc. This can isolate toxic smoke and fire gases or prevent their distribution throughout the areas served by the duct system.

USB Dongle Model

Service Company feature is available in all the LF-X500 series of control panel, the LF-5814 encrypted USB is used to enable this service. The Company ID and Engineer’s name are encoded in the USB in such a way that only this user can access it and those who are unauthorized cannot. When the USB is plugged-in on the PC, in the setting of LF-5810, it will show the Company ID and Engineer’s name, that means the encryption is available on your database. When the database is downloaded to the control panel, it will enable the Service Company setting. It is recommended that each distributor shall possess this item to protect the system against unauthorized user.

Remote Indicator

remote indicator is an attractive device used in installations where a detector going to alarm is likely to occur behind a locked door, inaccessible rooms, or in a ceiling void to provide indication of the activation of a fire detector.

Intelligent PSU

LF-X24-5A Intelligent PSU is to solve the problem of power supply and development of field equipment, power output is about 132.5W(DC26.5V/5A). The main function of the power supply for the conversion of AC220V voltage to DC26.5V, and with the preparation of electric power supply and power charging function, the standby battery provides the output of the DC24V/12Ah in the AC220V to stop the power supply, start to work with the equipment on the spot to play the role of continuation.

Dual Loop Card Model

The LF-LC5004 is a dual loop card used to expand the loop capacity of the control panel, each loop can accommodate up to 254 addressable LIFECO LF-X500 CIE compatible devices such as optical smoke detectors, heat detectors, call points, modules and sounders in any combination. The transmission path is fully monitored such as in the case of a short or open circuit fault and fault is reported to the control panel distinctively per each loop. The loop card has a built-in DC surge protection against 4kA lighting current. The LF-LC5004 is panel mount type that can be installed in any available loop port, the control panel will automatically assign the loop number when powered-on.

Network & Communication card

The LF-NC5004 is multiple communication protocols such a USB, Ethernet, Can Bus, RS485/RS232 on a single card intended to use in LF-X500 series control and indicating equipment. These four protocols synchronously working separately, the USB port is used for programing the control panel by uploading the data base form the laptop and for interfacing the Graphic Monitor Center (LF-5812) server and client machine, while the CAN Bus signal is for the networking that can support up to 512 control panel in one ring. The Ethernet port is used for IP networking if required. The RS485/RS232 is use for interfacing third party system such as building management system.

CanBus to Single-Mode

LF-MC201 allows you to extend CAN bus communication at distances up to 20 km depending on the type of optical fiber. The converter has an external 5VDC power supply and a wide operating temperature range from -40°C to 75°C which in combination with a metal housing allows it to be used in industrial conditions.

Manual Call Point

The Manual Call Point is designed to release a signal for a fire condition to
the Fire Control Panel upon manual activation by pressing the place signed
with arrows.
The light indication for activating the manual call point is provided by a red
LED. There is a possibility for testing by a special key.

Siren & Siren with Strobe

The LF-SI/SS Siren and Siren with Strobe are designed for maximum performance, reliability and cost effectiveness. It adopts a built-in integrated circuit, a piezoelectric sounder and high intensity strobe which when combined, produces high energy conversion efficiency for effective output of light and sound while utilizing a minimum amount of power.

Sounder with Beacon

A product designed for conventional fire alarm systems, it is an ideal solution for environments that require a discreet but affective device.Used as an ancillary visual alarm in fire systems; LIFECO Sounder with Beacon is suitable for conventional and 2-wire fire systems as well for general alarm and signalling systems.As with the wider LIFECO range, the product is designed to fit any recessed single gang box, giving a flush finish or surface mounted using the default surface box.

Datasheets
Intelligent Optical Smoke Detector

The LF-X5100 Intelligent Addressable Optical Smoke Detector is the ideal device for most applications, due to its spiffing linear response to a wide variety of different types of smoke patterns. The unit manufactured the sensitivity requirement of EN 54 part 7, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs. The unit incorporates an intelligent processor that provides Algorithm map, inbuilt A/D converter, Drift compensation, and Self-Diagnosis and History log.

Intelligent Heat Detector

The LF-X5110 Intelligent Fixed and Rate of Rise Heat Detector is reliable for application in places where may have high dust level or smoky environments, making a normal smoke detector undesirable. The unit manufactured base on the sensitivity requirement of EN 54 part 5, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs. The unit incorporates an intelligent processor that provides inbuilt A/D converter, and Self-Diagnosis and History log.

Intelligent Multi-sensor Fire Detector

The LF-X5120 Intelligent Multi-sensor Fire Detector is the ideal device for most applications, due to its spiffing linear response to a wide variety of different types of smoke patterns and combining with heat sensing sensor for temperature response. The unit manufactured base on the sensitivity requirement of EN 54 part 29, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs. The unit incorporates an intelligent processor that provides Algorithm map, inbuilt A/D converter, Drift compensation, and Self-Diagnosis and History log.

Datasheets
Addressable Detectors Base

A “Detector Base” in the context of fire detectors is a component that serves as the mounting and connection point for a fire detector device. It provides physical support for the detector and facilitates electrical connections for power and communication with the fire alarm system.

Addressable Sounder Strobe Base

Addressable Sounder Strobe Base is an alarm warning device used to notify persons in the vicinity of the occurrence fire emergency in order the person to take appropriate measures. The unit adopt multi-application device starting from the types, parameters and wiring layout in single unit. The LF-X5302 Addressable Sounder Strobe Base is powered by the communication bus. The LF-X5302 can change into different encoding modes such as Single-encoding Mode, Dual-encoding Mode 1 and Dual-encoding Mode 2 using a programming tool. And it has different starting modes such as started by a detector, a controller or other front-end linkage. In addition, the alarm tone can be configured according to the requirement from 17 different tones.

Base Mount Short Circuit Isolator

The LF-X5232 manufactured base on the requirement of EN 54 part 17, European Standard. In the event of short circuit on the detection loop the LF-X5232 Isolators either side of the loop will detect the problem and open circuit and isolates the faulty part of the loop, enabling other devices on the unaffected part of the loop to operate normally. The isolator will continue to monitor for the fault to be repaired, once the fault is cleared the isolator will automatically reinstate the effected part of the loop.